Can you run wires through a insulated wall?

Quick Answer

Yes, it is possible to run wires through an insulated wall, but special considerations must be taken. The key factors when running wires through insulation are:

  • Using wiring approved for insulation contact
  • Ensuring no gaps or compression in the insulation
  • Not overloading the wire ampacity
  • Properly securing and protecting the wire

With proper planning and execution, electrical wires can be safely and effectively run through insulation without compromising fire safety or energy efficiency. Proper installation is critical.

Can You Run Romex Through Insulation?

Romex is a common type of electrical wire used in residential settings. Technically, National Electrical Code (NEC) approved Romex cables can be run through insulation. However, there are important caveats:

  • The cable must be rated for direct insulation contact.
  • Cables must be protected from damage and secured at proper intervals.
  • Insulation must maintain full contact with no gaps or compression.
  • Ampacity derating may be required if multiple current-carrying conductors are bundled.

Standard NM-B Romex cable has a nylon outer sheath that resists moisture and insulation damage. But it is not intended for direct contact with insulation. Running it through insulation could overheat the conductors.

Insulated wires like NM-B-IC (insulation contact) or UF-B Romex are designed to run through insulation without overheating. They meet NEC safety standards for this application when properly installed.

Can You Run THHN Through Insulation?

THHN wire stands for Thermoplastic High Heat-resistant Nylon coated wire. It has a thin nylon outer layer that resists heat, moisture, and damage.

Like Romex, standard THHN wire is not rated for direct contact with insulation. However, THHN-2 wire is designed and rated specifically for insulation contact.

So THHN-2 can be safely run through properly installed insulation. Key considerations include:

  • Maintaining wire ampacity through derating if necessary.
  • Protecting wires from damage using conduit or proper securing.
  • Ensuring insulation fully surrounds the wire with no gaps or compression.
  • Using approved insulation materials like fiberglass and mineral wool.

With proper precautions, THHN-2 wire can be run through wall insulation safely. But standard THHN wire should not contact insulation directly.

Can Speaker Wire Be Run Through Insulation?

Speaker wire is used for audio signal transmission to speakers. It has two core insulated wires and an outer plastic jacket.

Technically, speaker wire can be run directly through insulation if:

  • The insulation does not compress or damage the wire.
  • Any contact points are protected against abrasion.
  • Wires are secured properly.
  • Prolonged contact does not generate excessive heat.

However, building codes and electrical safety standards often require wiring to be run through conduit or protected from damage. Speaker wires also need to be separated from AC power lines.

For in-wall applications, running speaker wire through fire-rated insulation contact (IC) conduit is the safest, most code-compliant method. The conduit protects the wire and allows replacement if needed.

Can Coaxial Cable Touch Insulation?

Coaxial cable is commonly used for cable TV, satellite, and antenna connections. The copper center conductor is surrounded by insulation and a braided outer shield.

Like other wires, coaxial cable can technically touch insulation if certain conditions are met:

  • The jacket is moisture and heat resistant.
  • The insulation does not compress or abrade the cable.
  • Prolonged contact does not raise temperatures excessively.
  • The cable is properly supported and secured.

However, building codes often require coaxial cables to be run through conduits or be rated for insulation contact. Moisture and accidental damage are also concerns.

RG-6 coaxial cable with a PVC jacket can handle some insulation contact. But conduit provides more protection and makes replacing cables easier. Direct burial coaxial cables are also designed to run through insulation.

Can Electrical Wires Touch Insulation?

In general, electrical wires should not touch insulation unless they are specifically rated for it. Insulation can present the following risks:

  • Heat buildup from sustained contact, especially in bundled wires.
  • Moisture wicking to the wires if the insulation gets wet.
  • Damage to wire jackets from compression or abrasion.
  • Difficult access for inspection, repairs, or replacement.

However, new wire types like NM-B-IC and THHN-2 are designed for insulation contact. With proper ampacity derating and installation, these wires can safely run through insulation.

Otherwise, it’s safest to run electrical wires through conduit or use insulation standoff’s. Wires should not be buried in insulation unless approved for that purpose. The National Electrical Code (NEC) provides guidance on wiring insulation requirements.

Can Low Voltage Wires Contact Insulation?

Low voltage wiring operates at less than 50V, commonly 24V. This category includes speaker, security, landscape, and other low power wires.

These wires generate minimal heat and voltage, so they can physically contact insulation if properly installed. Direct burial low voltage landscape wires are designed to run through insulation.

However, low voltage wires still need protection from damage, moisture, and compression. Optimal installation methods include:

  • Running wires through conduit or sleeving.
  • Leaving slack to prevent strain.
  • Securing wires properly using insulated standoffs.
  • Using moisture-resistant jacketed cables.

Low voltage wiring can run through insulation but should not be buried in loose insulation fill. The wires need support and protection for best performance and safety.

Can Ethernet Cable Touch Insulation?

Ethernet cable contains four twisted pairs of insulated, stranded copper wires. It is used for wired internet connections.

Technically, bare Ethernet cable can make contact with insulation. The twisting and interior insulation minimize interference. However, there are still risks involved:

  • Damage from compression around sharp corners or wood studs.
  • Moisture wicking into the cable if insulation gets wet.
  • Heat buildup around multiple bundled cables.
  • Abrasion of the jacket from friction.

Running Ethernet cable through conduits or sleeves is the optimal method. Plenum-rated Ethernet cable has extra fire resistance for use in ceilings and walls. Properly secured cables can also be routed through insulation while supported at regular intervals.

Ethernet cables can touch insulation but not be buried in loose fill. Care must be taken to minimize moisture and physical damage to the jacket.

Do Electrical Cables Need to be Rated for Insulation Contact?

According to the National Electrical Code (NEC):

  • Cables used in wet or damp locations must be suitable for use in these locations.
  • Cables installed in thermal insulation must be rated for this application (e.g. NM-B-IC).
  • Cables installed parallel with insulation must be rated for that purpose.
  • Cables in hollow spaces where loose insulation may gather require protection.

So in many cases, yes – cables run through or along insulation must be rated for insulation contact. They need sheaths and jackets resistant to moisture and heat buildup.

Conduit, ducts, or rated insulation contact wires should be used where wiring passes through insulation. Derating the ampacity may also be required with multiple current-carrying conductors.

When Can Wires be Buried in Insulation?

Wires should generally not be buried in loose insulation. The exception is direct burial cables designed for that purpose, like:

  • UF-B Romex (Underground Feeder)
  • Dbr (Direct Burial)
  • Tray cable
  • Some Low voltage landscape lighting wires

These wires have an extra moisture-resistant insultation and are rated for wet/damp locations. They can be buried in insulation without conduit.

Otherwise, it’s safest to run wires through conduit in insulation. Or use approved insulation contact wires like NM-B-IC or THHN-2 properly supported on wire hangers.

Do not bury standard NM, THHN, coaxial, CAT5, or speaker wires directly in insulation. Follow all NEC codes for wire insulation contact.

Can You Run Wires Through Spray Foam Insulation?

Spray foam insulation is applied wet and expands to fill cavities. This causes concerns with embedding wires:

  • Wires can become buried and difficult to access.
  • Foam drying and curing generates heat that can damage wires.
  • Moisture is trapped until the foam fully cures.
  • Plastic pipes and wires provide paths for foam to spread

Because of this, wiring should be routed through spray foam insulation only if:

  • It is rated for wet locations and insulation contact.
  • It is run through conduit or sleeves embedded in the foam.
  • A thermal barrier coats wires before foam is applied.

UF/DBR wires or THHN/THWN-2 wires in conduit can be safely run through spray foam. But extra precautions are needed compared to firmer insulations. All manufacturer guidelines and electrical codes must be followed.

How to Run Wires Through Existing Insulation

Running new wires through existing wall or ceiling insulation requires care not to disturb the insulation. Options include:

  • Cut narrow slits in the outer vapor barrier facing to thread wires through before patching the facing.
  • Use a long flexible drill bit to bore through top plates into the cavity, then fish wires through.
  • Remove a section of drywall to access the stud bay and run wires before replacing insulation and drywall.
  • Use insulated wall push pins to temporarily hold wires against cavity surfaces above the insulation.
  • Blow new insulation over existing to embed conduits/wires, then patch facing.

The goal is minimizing air gaps in the insulation. Seal penetrations with spray foam or caulk and use approved insulation-contact wiring. Faced fiberglass batts provide a vapor barrier that should not be excessively disturbed.

Wiring Precautions When Running Through Insulation

Some key wiring precautions when routing through insulation:

  • Use only approved cable types rated for insulation contact
  • Keep insulation in full contact with cables, no gaps or compression
  • Prevent moisture damage with vapor barriers
  • Properly support and secure cables to avoid strain
  • Separate and shield power cables from data cables
  • Oversize conduit for easy wire pulling and replacement
  • Label wire runs for identification
  • Maintain required clearance distances between cables
  • Firestop any penetrations through firewalls

Install insulation carefully around electrical boxes and junctions. Don’t bury splices in insulation. Follow all NEC requirements and manufacturers’ specifications when running wires through insulation.

Conclusion

It is possible to run electrical wiring safely through insulation, but the type of wiring and installation method are critical. Only wiring specifically rated for insulation contact should be embedded in or surrounded by insulation. Otherwise, conduit should be used for protection. Care must also be taken to prevent compression, moisture ingress, overheating, and damage to the wiring. With proper materials and installation, electrical wiring can coexist with insulation to safely deliver power and signals throughout a building. Rigorous adherence to electrical codes and standards is required. When in doubt, consult a qualified electrician.

References:

  1. National Electrical Code (NEC) Articles 300.22, 334.15, 760.53 – Wiring in Insulation.
  2. Underwriters Laboratories (UL) 263 – Safety Standard for Fire Test for Building Wire and Cable.
  3. Insulated Cable Engineers Association (ICEA) Standards for Insulation Contact Wiring.
  4. NEMA WC 70 – Power Cables Rated 2000V or Less for the Distribution of Electrical Energy
  5. IEEE Standard P1215 – Standard for the Testing, Design, Installation, and Maintenance of Electrical Wire and Cable in the Dynamic Space, Launch, and Flight Environment.